Partial discharge characteristics of epoxy insulation surface under AC/LI superimposed voltages in SF<sub>6</sub>/N<sub>2</sub> gas mixtures
Yang Zhou,Xutao Han,Yanxin Wang,Lin Niu,Xuanrui Zhang,Yan Qin,Junhao Li
DOI: https://doi.org/10.1109/TDEI.2024.3381089
IF: 2.509
2024-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:In this article, the partial discharge (PD) excitation characteristics of SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
/N
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>
gas mixtures on the epoxy insulation surface under AC/LI (Alternating Current and Lightning Impulse) superimposed voltages are investigated. The phenomenon of PD excitation in SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
/N
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>
gas with 20% SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
content is explained in detail. The effects of SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
/N
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>
gas mixtures ratio and the polarity on the PD characteristics under subsequent AC voltage are analyzed. It found that under the influence of AC/LI superimposed voltages, there are significant differences in the PD initiation characteristics between SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
/N
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>
gas with SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
content less than 60% and pure SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
. In SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
/N
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>
gases, the AC superimposed phase that can initiate subsequent discharge is larger, and when superimposed voltages is applied in the positive (or negative) half-cycle of AC to initiate discharge, in pure SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
, the discharge only occurs in the subsequent AC’s negative (or positive) half-cycle. However, in SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
/N
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>
gas mixtures with SF
<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>
content less than 60%, the discharge can occur in both the positive and negative half-cycles of AC. In addition, the PD phenomenon after AC/PLI superimposed voltages is more prominent than AC/NLI superimposed voltages. The severity of PD under subsequent AC increases with the decrease of AC voltage duration experienced from the superposition moment to the first zero crossing point of the AC voltage.