Analysis of Partial Discharge Spectrum Based on Ultra-High Frequency Detection Method

Qiao Guan,Baofeng Xi,Chen Zhang
DOI: https://doi.org/10.1088/1742-6596/2030/1/012096
2021-01-01
Journal of Physics Conference Series
Abstract:Oil immersed power transformer is the most widely used large power transformer in power system and its insulation structure is mainly composed of oil, paper and other solid insulation materials. Partial discharge monitoring is an effective means to find dielectric faults of transformer in an early stage of development. Ultra-high frequency(UHF) partial discharge detection technology has high detection frequency and strong anti-interference ability, which is suitable for transformer online detection. In this paper, five typical transformer discharge models are built, and the discharge spectra of each model are measured by a UHF sensor. The test results show that the surface discharge and wedge discharge most occurs near the voltage peak, the discharge phase distribution of floating part discharge is very wide, the internal air gas discharge mostly occurs in the area where the absolute value of voltage increases, and the point-to-plane discharge has a typical polarity effect.