Research of Induced Voltage and Current on 750 kV Double Circuit Line on Same Tower and Selection of Grounding Switch

OU Xiao-bo,HAN Yan-hua,GONG Peng,JI sheng-chang
2011-01-01
Abstract:When one of double circuit transmission lines on the same tower is in operation and the other is for examining and repair, induced voltage and current will occur on the latter line which is derived from electrostatic induction and electromagnetic coupling. To ensure the reliability and safety of the lines, the grounding switch must have a capacity of interrupting inductive current. The induced voltage and current of the 750 kV double circuit lines on the same tower as well as the TRV when switch grounding fault occurs are calculated by EMTP, and it provides guiding opinions for selecting grounding switching of the 750 kV double-circuit transmission line.