Influence of Typical Defects on Insulation and Gas Production Characteristics of Oil-Impregnated Paper Bushing
Lilan Liu,Peng Liu,Yuelin Fan,Qingsong Wu,Zehua Wu,Qingyu Wang,Zongren Peng
DOI: https://doi.org/10.1109/tdei.2024.3355360
IF: 2.509
2024-01-01
IEEE Transactions on Dielectrics and Electrical Insulation
Abstract:Potential defects in oil impregnated paper (OIP) bushing during manufacturing or transportation may further deteriorate and develop under long-term operation, affecting the insulation, and leading to the transformer damage and the power outage. In this article, scaled models were designed and produced according to 550kV OIP bushing, and typical defects, including the plate wrinkle defect, the plate deviation defect, the plate damage defect, the moisture defect, and the end shield ungrounded defect, were set in the models. Based on a long-term high-voltage experiment platform, a 45-day simulated operation was applied on the defect models, as well as the non-defect one. The tests of partial discharge, frequency domain dielectric response, and dissolved gas in oil were carried out every few days. The results indicate the models with the plate wrinkle defect and the moisture defect had the most significant changes, with enhancing partial discharge, increasing dielectric loss, and growing dissolved gas in oil. The capacitance of the end shield ungrounded defect model is much different, which can be quickly recognized. The results of others have not changed much, perhaps due to the absence of discharge during long-term experiment. Additionally, the combination of three tests can provide more valuable references.
engineering, electrical & electronic,physics, applied