Research on Deterioration Mechanism of Oil-paper Insulation of 220 Kv Current Transformer

Guowei Zhou,Qilong Wang,Yiwen Shi,Xiangrong Chen
DOI: https://doi.org/10.1109/ei252483.2021.9713025
2021-01-01
Abstract:The electric and thermal combined deterioration mechanism of the oil-paper insulation of the 220 kV current transformer with different thermal aging times is investigated. The breakdown strengths and breakdown time are obtained with different dwelling times. Furthermore, the life exponents under different temperatures and different aging times are evaluated by a step-by-step increasing voltage test. Finally, the four multi-factor aging models about the remaining life, the electric field, and the temperature are developed. It is shown that the breakdown voltages and the breakdown time decrease rapidly with the increase of the temperature or the thermal aging time, whereas the breakdown time increases with the increase of the dwelling time. The life exponent of the oil-paper is more sensitive to the thermal aging at room temperature, whereas it is more sensitive to the temperature compared to the thermal aging when the temperature exceeds 50 °C. The expected life of the oil paper decreases with the increase of the temperature and thermal aging time. Moreover, the remaining life is inversely related to the electric field and the temperature in the three multi-factor aging models. CRINE model has the best fitting accuracy among the three models. The results can provide theoretical support for the safe operation of the 220 kV current transformer.
What problem does this paper attempt to address?