Influence of Smoothing Reacteor Arrangement on Transients of Converter Station for ±500kv Double-Circuit HVDC System

Manling Dong,Shijun Xie,Dandan Zhang,Hengxing He,Minghui Bao,Junjia He,Ying Huang,Xiaolin Li,Zongyuan Cai
DOI: https://doi.org/10.1109/pes.2010.5589913
2010-01-01
Abstract:For HVDC transmission system, the smoothing reactor has two structural types; oil-immersed core reactor and air-core reactor. The former needs to concentrate installed on DC-line, and the latter can be arranged flexibly on both pole line and neutral line. According to the different arrangements of smoothing reactors, the system steady-state performance and over-voltage of converter station have some difference. In this paper, the influence of different smoothing reactor arrangements on the system steady-state performance and converter station over-voltage performance of Xiluodu-Guangdong ± 500kV double-circuit HVDC project is analyzed by using ATP/EMTP. A reasonable arrangement of smoothing reactor is proposed, which aims at both maintaining reliability and reducing costs.