Failure analysis on abnormal leakage of radiator for high-speed train transformer

An-Xia Pan,Yi Gong,Zhen-Guo Yang
DOI: https://doi.org/10.1016/j.engfailanal.2021.105673
IF: 4
2021-01-01
Engineering Failure Analysis
Abstract:•The root cause of abnormal and premature leakage of the radiator of high-speed train transformer was comprehensively studied.•Chloride and sulfide induced pitting corrosion due to accumulation of dust and acid rain from environment was found to be main failure mechanism.•Inappropriate design of the fin structure and unqualified brazing process were the root causes to initiate pitting corrosion.•Countermeasures including optimization of the air-side fin structure and improvement of the brazing process were proposed.
What problem does this paper attempt to address?