Failure Analysis on Water Wall Tube Burst of Heating Furnace

meng qingwu,ren liming,li jiaxin,meng fanqi,yu hang
DOI: https://doi.org/10.3969/j.issn.1007-015X.2018.04.012
2018-01-01
Abstract:In order to find out failure causes of water wall tube burst of a steam heating furnace in a chemical plant,microstructure of inner and outer tube,corrosion products and metallographic structure were analyzed by SEM and other testing instruments.The results showed that oxidation fatigue crack was the primary cause,which was caused by long-term high temperature oxidation environment and alternating load induced by frequent start and stop working conditions,besides,the secondary causes were thick oxide layer on inner and outer tube walland pearlite spheroidization in metallographic structure.