Overheating and Failure Analysis on the Fire Tube of Heating Furnace after Scaling

meng fanqi,meng qingwu,yao yilan,ren liming,zhang xiaoxue
DOI: https://doi.org/10.3969/j.issn.1007-015X.2017.02.001
2017-01-01
Abstract:In order to find out the causes of a burning leakage accident of fire tube in oil heating furnace,fouling and microstructure of the fire tube were analyzed and metal temperature under the fouling of the same kind fire tube was detected. The results showed that fouling on the surface of fire tube led to metal overheating and damage of spheroidizing microstructure,which caused the decrease in the bearing capacity of fire tube. Under the pressure of furnace for a long time,the fire tube crept,swelled and became thinning,which resulted in the damage and leakage. Several measures were put forward to avoid the occurrence of similar accidents,such as detecting and evaluating the microstructure damage,replacing with the heat resistant steel and shortening the cleaning period.
What problem does this paper attempt to address?