New Fault Location Algorithm for Double Transmission Lines on a Same Tower

ZHAO Yong-xian,CAO Xiao-guai,LIU Wan-shun
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.04.015
2005-01-01
Abstract:This paper compares and analyses various types of main fault location algorithms and puts forward a new fault location algorithm for double transmission lines on a same tower. The algorithm adopts the line' s model of distributing parameter, uses two-end data and six-order component and considers the problem to identifying inaccurate parameter. EMTP simulation demonstrates the correctness and validity of the proposed algorithm. The precision of location identified by the proposed algorithm is quite high and the algorithm is not affected by transition fault impedance, load current and method of system operation. It does not demand two-end data in synchronism and has preferable self-adapting ability for inaccurate line parameter.
What problem does this paper attempt to address?