A novel detector of ground fault and ferro_resonance in ungrounded distribution system

Jian-ze WANG,Qi-tao WU,Yan-chao JI,Zhuo LIU
DOI: https://doi.org/10.3969/j.issn.1674-3415.2001.05.010
2001-01-01
Abstract:In ungrounded distribution system the single-phase-grounding and the ferro-resonance caused by the PT (Potential Transformer) are of the frequent accidents. In both of the cases above, the shift voltage of neutral point often appears. So one does not differ from the other easily, especially for the fundamental frequency ferro-resonance. It is the primary cause that the present fault-feeder detector and the PT-resonance-eliminator judge wrongly sometimes. To overcome the disadvantage above, a new general criterion, which applies to detect both the fault-feeder and the PT resonance, is presented in this paper. This criterion utilizes the character of the zero-sequence current in the both cases. And the novel detector of ground fault and ferro-resonance, which is developed based on it, works efficiently in practice.