PROTECTION FOR DETECTING SINGLE-PHASE-TO-GROUND FAULT FEEDER BASED ON SYNTHESIS INCREMENT PRINCIPLE IN RESONANT GROUNDED POWER DISTRIBUTION SYSTEM WITH ARC-SUPPRESSION WITH MAGNETIC BIAS

蔡旭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2003.20.015
2003-01-01
Abstract:Featured in this paper is an in-depth analysis of single-phase-to-ground fault through a resistance in resonant grounded power distribution system. The zero sequence voltage, the zero sequence current, and the zero sequence current synthesis increment are defined. Vectors of zero sequence voltage, zero sequence current and its synthesis increment and their change tracks with different grounding resistance are shown. The relation between synthesis increment and the zero sequence voltage percent at the time before arc-suppression coil current changes and the change quantity is found. The criterion based on the principle of synthesis increment for detecting grounded feeder is established. A device based on the principle mentioned above for detecting grounded feeder is developed. The black diagram of its hardware and the flow of its software are given. The zero sequence current transformer with a coil for self check-up is used, and the cell used for checking up the current transformer and rectifying its error is developed. For over one-year site operation, it is shown that the device based on the principle mentioned above can detect fault feeder accurately and reliably.