Prestrike Electric Field Characteristics when Switching on Inrush Current in 40.5kV VCB

Haoqing Wang,Yingsan Geng,Jinyang Lin,Zhiyuan Liu,Xiangyang Li
DOI: https://doi.org/10.1109/deiv.2018.8537006
2018-01-01
Abstract:Nowadays the phase controlled switching is a preferred method for capacitive switching. Thus the prestrike characteristics are important issues for the control strategy. The objective of this paper is to determine the prestrike electric field characteristics for the contact materials manufactured by infiltration and arc-melted preparing technology in the capacitive switching of 40.5kV vacuum circuit breaker (VCB). In the experiment, CuCr50 and CuCr40 contacts with a diameter of 50 millimeters were prepared by infiltration and arc-melted technology respectively. L-C oscillating circuit generated inrush current with a frequency of 207Hz and with a peak of 6.48kA, while the applied voltage was 46.3kV which is equivalent to the peak voltage for a 35kV three-phase network whose capacitive voltage factor is 1.4. The experimental results show that the measured dynamic prestrike field derived from test data is lower than that of theoretical static breakdown field in each closing operation. While the values of prestrike voltage for all six test VI are nearly the same when the prestrike gap is lower than 12mm, and then they become different beyond 12mm. In addition, the relations of prestrike voltage versus prestrike gap follow the second-order exponential distribution for all six test VI.
What problem does this paper attempt to address?