Experiment Researches on Cold State Dielectric Recovery Characteristics in High Voltage SF6 Circuit Breakers

LIN Xin,WANG Feiming,LIU Weidong,XIA Yalong,XU Jianyuan,ZHONG Jianying
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.150991
2016-01-01
Abstract:Dielectric recovery characteristics during operation of high voltage SF6 circuit breakers were studied by tests. The test circuit of dynamic breakdown characteristics was built. Circuit breaker closing and opening dynamic breakdown voltage curves under the positive and negative polarities were obtained. Impacts of inflatable pressure and closing speed to dielectric recovery characteristics were analyzed. The breaking dielectric recovery rate and the closing pre-strike time under different experimental conditions were given. The results show that: the positive polarity breakdown voltage is greater than that of negative polarity of SF6 gas. The impact of closing speed on the closing pre-strike characteristic is significant. The maximum closing pre-strike time is 1.18ms under closing speed 6.6m/s. The maximum closing pre-strike time is 2.21ms under closing speed 4.7m/s. It can be seen, to improve the closing speed is an effective method to control the pre-strike time. Whenp=0.7MPa andp=0.5MPa respectively within 0.5ms and 1ms after contact separation, breakdown may occur again. Therefore, the arc should be avoided to extinguish in this time range.