Experimental Study on Fast Isolating Switch with Vacuum Multi-breaks

Bin Liu,Haibo Yu,Xiaobo Zhang,Pengcheng Xie,Jie Xiong
DOI: https://doi.org/10.1109/peac.2018.8590222
2018-01-01
Abstract:Fast isolating switch is one of the key components of Hybrid DC circuit breaker. It is difficult for conventional breakers to provide such a fast operating speed when the switching time is within a few milliseconds. In this paper, based on the study of the vacuum switch, focusing on the application of small vacuum gap in DC isolation, arcless breaking situation, a series of experiments were designed. After solving the problems of synchronous as well as voltage distribution in every break, a 200kV DC fast isolating switch with less than 3ms switching time is developed, And through the whole test of DC circuit breaker.
What problem does this paper attempt to address?