Analysis on Zero Sequence Current Distribution Characteristic of Grounding Faults Occurred in Double-Circuit Transmission Lines on the Same Tower

曾耿晖,蔡泽祥,陈桥平,刘为雄
DOI: https://doi.org/10.13335/j.1000-3673.pst.2011.11.037
2011-01-01
Abstract:The distribution regularity of zero-sequence current, which appears during external and internal grounding faults occurred in double-circuit transmission lines on the same tower under different operation modes, different zero-sequence mutual inductance and different fault locations, is analyzed. For external grounding faults, the impact of different zero-sequence impedance of double-circuit transmission lines on the same tower is mainly considered; for internal grounding faults, the impacts of zero-sequence mutual inductances and fault locations under following conditions are considered: parallel operation of both transmission lines; one transmission line is energized and in the stand-by state while the other one is artificially grounded for the maintenance. The effects of "zero-sequence magnetic assist" and "zero-sequence degaussing", which are caused by the flowing of zero-sequence currents of both transmission lines on the same tower in the same direction and by those in the opposite direction respectively, lead to variation of distribution regularity of zero-sequence currents, and in extreme circumstance the out-of-limit of the first zone of zero-sequence over-current protection may occur. Based on practical calculation examples of Guangdong power grid, the setting measures are put forward to avoid the out-of-limit of the first zone of zero-sequence over-current protection for double-circuit transmission lines on the same tower. It is also proposed that in the setting of the first zone of zero-sequence over-current protection for double-circuit transmission lines on the same tower, the comprehensive effects of operation modes of double-circuit transmission lines on the same tower, the extent of zero-sequence mutual induction and fault locations should be taken into account to avoid the malfunction of the first zone of zero-sequence over-current protection of adjacent healthy transmission lines due to the affect of mutual induction while grounding fault occurs in another circuit of transmission lines .
What problem does this paper attempt to address?