Transient analysis of the output short-circuit fault of high power and high voltage DC power supply

Zhi-gang YANG,Jian ZHANG,Yi-yun HUANG,Xu HAO,Hao-zhang SUN,Fei GUO
DOI: https://doi.org/10.3969/j.issn.0254-6086.2014.04.012
2014-01-01
Abstract:The transient conditions of output short-circuit fault of high voltage DC power supply was introduced, and the energy of power supply injecting into klystron during the protection process of three-electrode gas switch were analyzed and calculated in detail when klystron load happening electrode arc faults. The results of calculation and simulation are consistent with the results of the experiment. When the output short-circuit fault of high voltage power supply occurs, switch can be shut off in the microsecond, and the short circuit current can be controlled in 200A. It has verified the rapidity and reliability of the three-electrode gas switch protection, and it has engineering application value.