Study on Measurement of Grounding Current and Its Characteristics for Composite Insulator

Xiao-yang MIAO,Sheng-chang JI
2008-01-01
Abstract:The major method now for detecting pollution condition of composite insulator is to detect leakage current.This method needs to install the current transducer on insulator,which increases the measurement difficulty and danger.The paper presented the method to detect the pollution degree of composite insulator surface by measuring its grounding current.To test and verify the practicability of detecting the pollution degree of composite insulator surface,it is necessary to study the characteristics of composite insulator grounding current.In this paper,three kinds of measurement circuit were set up to measure the grounding current,the body leakage current and the surface leakage current separately of the composite insulator,and under clean and pollution condition the three kinds of current of the composite insulator that had mentioned before were measured and analyzed respectively by comparing the three kinds of current.The results show that the grounding current and the surface leakage current amplitude of pollution composite insulator increased obviously compared with the clean condition,and they almost have the same increase,as well their harmonic component decreases greatly with the same rate.However,body leakage current almost has no change compared with the clean one.The pollution degree of composite insulator surface can be detected by measuring grounding current on the insulator grounding line.