WANG Bin,LIANG Xi-dong,ZHANG Yi-bo,LUO Bing,LI Zhen-yu,LIU Ying-yan,ZHOU Yuan-xiang
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.09.034
2009-01-01
Abstract:A natural pollution was tested to study the pollution and self cleaning characteristics of composite insulators and porcelain insulators (type: XP-70,XWP-70) energized with AC and DC voltage. Under the station’s condition,pollution differences between different insulators and different stresses mainly appeared on the insulators’ under-surfaces. During the main pollution period,upper-surface pollution accumulation rate of composite insulators was slightly higher than porcelain insulators’,while the under-surface pollution accumulation rate of composite insulators was 2 times as much as porcelain insulators’,under AC stress. The under-surface pollution ratio between DC stressed and AC stressed composite insulators was more than 5. For porcelain insulators,this ratio was 10. Pollution composition of insulators under DC and AC stress was analyzed. Two kinds of insulator cleaning processes by rain were observed in high and low precipitation. Self cleaning of composite insulators' under-surface was slightly hindered by hydrophobicity. The upper-surface pollution ratio between 3-year exposed and 1-year exposed composite insulators was about 1,while this ratio for under-surface under DC and AC stress were 2.2 and 1.4,respectively.