Natural Pollution Deposit Test of Polymeric Insulators Operated under DC Voltage

LI Zhen-yu,LIANG Xi-dong,WANG Bin,ZHOU Yuan-xiang
DOI: https://doi.org/10.3321/j.issn:1000-3673.2007.14.003
2007-01-01
Abstract:By use of self-built natural pollution test station, the experimental investigation of natural pollution deposit (NPD) features of polymeric insulators operated under DC voltage in northern China’s inland areas for two contaminated seasons is carried out. In this paper, the surface pollution deposit law of DC insulator shed, the influence of rainfall on pollution deposit (equivalent salt deposit density, ESDD) and non-soluble deposit density (NSDD), unevenness of pollution between top and bottom surface, dust to salt ratio of insulator surface, the orthogonal ratio of ESDD to NSDD and so on are analyzed. Research results show that not all rainfall achieves obvious purging efficiency on pollution deposited on insulator surface; both the amount of precipitation and rainfall intensity are important factors influencing purging effect; the maximum pollution degree of polymeric insulator occurs before rainy season in the summer, but not before spring rain. It is recommended that these features of pollution deposit should be adequately considered in the DC outdoor insulation design.
What problem does this paper attempt to address?