Abstract:In order to improve the accuracy and reliability of natural pollution test used in ultra high voltage direct current(UHVDC)insulator selection,a novel method that the leakage current online monitoring system were installed on the tested insulator strings was put forward by Tsinghua University,and the characteristic quantities of leakage currents monitored and calculated by the system were used as an important basis for UHVDC insulator selection.The results of UHVDC insulator selection based on this method were also given.Taking the insulators used in the natural pollution test in the Yun-Guang UHVDC Pollution test station as the objects of study,this pollution test began in May 2005and ended in September 2007,the tested insulator leakage current characteristics in this period were recorded and analyzed in detail.The weighted scores of leakage current characteristic quantities were calculated and used as an important basis for the selection of insulators,and the selection results based on the scores were given.The selection results by this method were compared with those by the artificial pollution tests,the comparison was more consistent.It is demonstrated that using the characteristic quantities of leakage currents monitored in the whole process to help the selection of insulators in the natural pollution test is feasible and effective.