Asynchronous Two-terminal Fault Location Method for Unbalanced Fault Based on Parameter Identification

MU Ka,WANG Fenghua,LIU Yadong
DOI: https://doi.org/10.13336/j.1003-6520.hve.20171031036
2017-01-01
Abstract:We put forward an asynchronous two-terminal fault location method for unbalanced faults,intending to eliminate fault location errors caused by asynchronous data and line parameter uncertainty.In the presented method,the asynchronous angle is eliminated based on sequence equivalent circuit analysis,and the fault location equations are established,in which the line parameters and the fault distance are the parameters to be identified.Then the equations are solved through a hybrid particle swarm and frog leaping algorithm to locate the fault point.Both simulation results and practical example using measured data show that the presented method is quite accurate and reliable without any false roots,and it is immune to line parameter uncertainty and can locate the fault point precisely only using unsynchronized fault data.The research may provide an important basis for the fault location of transmission lines.