A Cost-Effective Technique for PD Testing of MV Cables under Combined AC and Damped AC Voltage

Weisheng He,Qinghua Wang,Chenxi Huang,Hongjie Li,Deliang Liang
DOI: https://doi.org/10.1109/tpwrd.2016.2603446
IF: 4.825
2018-01-01
IEEE Transactions on Power Delivery
Abstract:This letter presents a cost-effective technique for partial-discharge testing of medium-voltage (MV) cables using a combined ac and damped ac (DAC) voltage. The combined ac and DAC voltage is generated by a conventional variable-frequency resonant test system and two high-speed switches. An experimental study and on-site test are performed to validate the proposed technique.