Analysis and Improvement of Design Defect in a Blowdown System of Sidewall Header

陈开潮,宋建彪,缪正清,田子平,勇继军,何华,顾金良,陆永德
DOI: https://doi.org/10.3969/j.issn.1004-8774.2001.05.014
2001-01-01
Abstract:Based on the investigation of local tube rupture, occurred several times in sidewall tube near front furnace door, the hydrodynamic analysis and calculation have been done to a blowdown system of sidewall header in a DZL6.0-l.25 steam boiler. It may be seen from the calculation that the essential reason is much lower velocity in the front section to re-sult in local tube rupture of watewall tubes connected to that section of header. The retrofit project has been proved from the calculation of the retrofit project that the lowdown hole in the front of header could effectively improve the water fluidi-ty in that aver of header during blowdown, removing the hidden danger of incrust ant deposition. After carrying out the retrofit project. the boiler has been operated several years safely. It has proved that the project is effective and successful.
What problem does this paper attempt to address?