Heat Transfer Characteristics of Two-Phase Cooling Loop Driven by Magnetic Pump

MA Yuezheng,MA Guoyuan,ZHANG Shuang
DOI: https://doi.org/10.11949/j.issn.0438-1157.20150551
2015-01-01
Abstract:An experimental setup of two-phase cooling loop driven by magnetic pump was built. The performance and start-up characteristics of the two-phase cooling loop are evaluated by the air enthalpy difference method. Experimental results show that the two-phase cooling loop driven by magnetic pump presents excellent performance for energy saving. Its start-up is quick and the system reaches a steady state after 600 s. The fluctuations of pressure and temperature in the system are caused by the superheat of the liquid refrigerant in the evaporator during the start-up. The cooling capacity of the system increases with the temperature difference, and increases rapidly with the mass flow rate and then decreases slowly. When the temperature difference is 10℃, the maximum cooling capacity is 3.429 kW and the energy efficiency ratio is 12.94. When the temperature difference is 25℃, they reach 9.241 kW and 29.7, respectively.