Experimental research and design of quasi two-stage heat pump system coupled with ejector

XU Shu-xue,MA Guo-yuan,PENG Long
2010-01-01
Abstract:In order to recover the available energy in the supplementary circuit of the quasi two-stage compression heat pump system,a quasi two-stage compression heat pump system coupled with ejector was brought forward,and the design method of which was presented and experimental setup was established with the evaporation temperature of-20 ℃.The results demonstrate that the heating energy efficiency ratio(EER) of the heat pump system with ejector can be 3%-5% higher than that without ejector while the heating capacity keeps nearly constant.The design method is helpful to design quasi two-stage heat pump coupled with ejector for different working fluids or other capacity compressors.
What problem does this paper attempt to address?