Experimental Research on Quasi Two-Stage Compression Heat Pump Using R32

Xu Shuxue,Ma Guoyuan,Zhao Bo,Liu Zhongliang
DOI: https://doi.org/10.3969/j.issn.0253-4339.2011.05.012
2011-01-01
Abstract:In order to investigate the heating performance of quasi two-stage compression heat pump system using R32,an experimental setup was established.The results showed that the discharge temperature of the quasi two-stage compression heat pump system was 10℃~20℃ lower than that of the single stage compression system,not exceeding the limit of 130℃,and the heat pump can steadily run for long time under the condensing temperature of 40℃ and the evaporating temperature varying from-10 to-5℃.The heating capacity of the quasi two-stage compression system with R32 is 12% higher than that of the single stage compression system,and the heating COPh depending on the intermediate vapor pressure is higher or lower than that of single stage compression system,and the suitable comparative value of intermediate vapor pressure is 0.9~1.1.
What problem does this paper attempt to address?