Experimental investigation on working performance of two-stage compression heat pump system with vapor injection

Zhang Sichao,Ma Guoyuan,Xu Shuxue
DOI: https://doi.org/10.3969/j.issn.1001-7100.2013.05.010
2013-01-01
Abstract:Taking the rolling piston compressor for example,a single two-stage compression heat pump system with vapor injection was constructed,the vapor injection parameters on the effect of system performance was experimentally researched.The experimental results show that with vapor injection system heating capacity can be higher 3~7%,discharge temperature can be lower 8~14℃,compressor efficiency can be higher 5~12%,high pressure stage volume efficiency can be higher 4~9% when compared to without.It provided experimental data and experience reference for the compressor design and heat pump system operation.
What problem does this paper attempt to address?