Simulation Study on Single-machine Two-chamber In-parallel Compression Refrigeration/Heat Pump System

Xu Shuxue,Ma Guoyuan,Liu Qi,Liu Zhongliang
DOI: https://doi.org/10.3969/j.issn.0253-4339.2013.06.001
2013-01-01
Abstract:In order to improve the working performance of vapor compression refrigeration /heat pump system,a new system named single machine two-chamber in-parallel compression refrigeration/heat pump system was provided.An analysis model was set according to the theory of thermodynamics.The variation of cooling and heating performance with side-stage suction pressure and the most favorable volume ratio of side-stage to main-stage have been calculated.The results show that,compared with conventional single-stage compression system,cooling and heating capacity can increase 29.6% and 29.2%;cooling EER and heating COP can increase 8.0% and 2.8%;the discharge temperature decrease 3~4℃.The most favorable volume ratio of side-stage to main-stage is 0.08~0.12.