Thermodynamic Analyses of Scroll Refrigeration System with Economizer

柴沁虎,马国远,江亿,夏建军
DOI: https://doi.org/10.3321/j.issn:1000-0054.2003.10.028
2003-01-01
Abstract:An improved performance simulation method was developed for scroll refrigeration systems which analyzes the entire compressing process with consideration of the key refrigeration system parameters to analyze the performance of a quasitwo stage scroll heat pump system. The results show that the optimal auxiliary inlets is right where the working chamber closes. Although the coefficient of performance and the discharge temperature change little as the locations of the auxiliary injections vary, the heating output is very sensitive to changes in the auxiliary injection locations. The simulation method can also be applied into screw compression heat pump systems.
What problem does this paper attempt to address?