EXPERIMENTAL STUDY ON TWO TYPES OF TRANSCRITICAL CO2 HEAT PUMP WATER HEATER SYSTEM

Qi Chen,Yang Tong,Mao Li,Zhijiang Zhu,Liming Tang,Guangming Chen
DOI: https://doi.org/10.3969/j.issn.0254-0096.2013.11.008
2013-01-01
Abstract:In order to study the effects of ejector on transcritical CO2 heat pump system performance, a prototype of heat pump was developed. In this paper, an experimental study on transcritical CO2 heat pump system with ejector (TRCS-EJEC) and without ejector (TRCS) was tested, and ejector performance was analyzed. The heat pump performance was investigated by changing cooling water flow rate and opening of the throttling valve. The experiment results showed that the compressor discharge temperature and compression ratio of the TRCS-EJEC is lower than that of the TRCS, and the ejector could increase the COP of the TRCS-EJEC up to 13.9% more than that of the TRCS. The COP of the TRCS-EJEC increased with the improvement of the ejector thermodynamical perfectness. Development of high efficient ejector was a critical factor on optimizing transcritical CO2 heat pump water heater.
What problem does this paper attempt to address?