Experimental research on boiling heat transfer mechanism of a pump-driven loop thermosiphon for R134a coolant
Tao Ding,Xiaoxuan Chen,Tian Zhao,Chaoyi Zhu,Hainan Zhang,Zhen Li
DOI: https://doi.org/10.1016/j.ijheatfluidflow.2024.109424
IF: 2.643
2024-05-19
International Journal of Heat and Fluid Flow
Abstract:With the development of big data and cloud computing, data centers have grown rapidly worldwide. A data center is a special building with high energy consumption. The energy consumption of traditional computer room air conditioning is assumed to be 45 % of the total energy consumption of the data center. Currently, the use of a loop thermosiphon as a cooling system is one of the most effective methods. Although loop thermosiphons have already been widely used, the boiling mechanism inside the evaporator needs to be studied further, particularly for pump-driven loop thermosiphons. In this study, we investigated the heat transfer and flow characteristics of a pump-driven loop thermosiphon. The inside tube diameter is 8.05 mm, the heat flux changes from 6317 to 28085 W/m 2 , and the mass flux changes from 437 to 1311 kg/m 2 s. First, the differences and similarities between pump- and gravity-driven modes are studied. Second, the matching relationship between the heat flux and mass flow rate is studied, and the mechanism of the flood limit for the pump-driven mode is illustrated. Finally, we compare different boiling correlations and propose a new correlation based on our experimental results.
engineering, mechanical,thermodynamics,mechanics