Design of Different Conductors in Different Phases on AC Transmission Lines
ZHANG Yun,ZHU Pu-xuan,ZENG Rong,HU Jun,HE Jin-liang,ZHANG Bo
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.12.032
2007-01-01
Abstract:In the designing of transmission lines,the conductor surface field strength is one of the restriction factors,in order to balance the charge and surface field of different phases,to increase the utilization ratio of conductors,and to reduce the investment,this paper introduces a new scheme that uses different conductors in border and middle phases.This paper also studies the electrical magnetic environment and parameters of the transmission line,the results show that this scheme can not only balance the surface field strength and electric charge of three phases,reduce total conductor section area,reduce total investment,but also increase the natural power per unit section area,but also significantly increase the utilization ratio of conductors.This paper also evaluates some factors in this scheme,such as the influence on the degree of imbalance,the over voltage level,communications,relay protection and failure distance location of the system.This new method has been applied in 330kV Luo—Da transmission line in Gansu province.