Analysis on Radio Interference from Double-Circuit of High Voltage AC Power Transmission Line under Different Arrangement of Phase Sequence by Excitation Function Method

LI Jun-jie,ZOU Jun,LI Ben-liang,YUAN Jian-sheng
DOI: https://doi.org/10.13335/j.1000-3673.pst.2010.06.004
2010-01-01
Abstract:The radio interference level from high-voltage power transmission line is one of the indices to evaluate electromagnetic environment of transmission line.By use of excitation function the radio interference levels from double-circuit transmission line under different phase sequences and different spacing between transmission lines are calculated.Calculation results show that for vertically arranged double-circuit transmission line,the radio interference level under the same phase sequence arrangement is the lowest;there is no evident difference among the radio interference levels corresponding to double-cuicuit transmission line with different phase sequence arrangement;for arbitrary number-circuit transmission line,it is necessary to calculate radio interference level by appropriate software.
What problem does this paper attempt to address?