Study of zero-sequence differential protection for transformer with Yn/Δ connection

Jiale Le Suonan,JunMin Zhang,Li Qiang Xu,Shufeng Feng Tan,ZaiBin Jiao,Bin Du,Xuan Zong Zhao
2010-01-01
Abstract:Because conventional differential protection is not sensitive enough to earthing fault and inter-turn fault, a differential protection method based on zero-sequence current is proposed which can still reliably operate when transformer internal weak fault occurs. Different from present scheme, the new protection scheme is constructed by using the zero-sequence current of each side. The zero-sequence loop current in the delta side can be calculated by the zero-sequence equivalent circuit according to typical CT configuration scheme and unknown current in delta side. Simulation with PSCAD and dynamic model data show that the proposed principle is correct. The comparisons between the performance of zero-sequence differential protection and conventional differential protection suggest that the zero-sequence differential protection has higher sensitivity to earthing fault and small inter-turn fault, and suffers less influence from inrush.