A novel phase comparison pilot protection scheme based on zero-sequence current of UHV auto-transformer

Kader ALIMJAN,Jia-le SUONAN,Arken YILIYAR,Hai-yun WANG,Yi-zhi TIAN
2014-01-01
Abstract:Zero-sequence-current-differential-protection-for-grounding-fault-has-the-advantages-of-high-sensitivity,-action-current’s-independence-with-transformer-tap-joint,-small-influence-from-inrush-current,-and-principle-simplicity.-It-is-widely-used-in-the-area-of-UHV-autotransformer-protection.-However,-the-zero-sequence-current-differential-protection-operates-due-to-responding-to-the-phase-sum-of-zero-sequence-current-in-three-sides-of-autotransformer,-which-is-badly-influenced-by-the-saturation-of-current-transformer-and-hard-to-set-the-threshold.-In-the-external-fault,-it-will-lead-to-mal-operation.-Based-on-this,-a-new-auto-transformer-pilot-protection-scheme-based-on-the-zero-sequence-current-phase-comparison-is-proposed.-The-fault-direction-can-be-determined-by-comparing-the-phase-shift-between-zero-sequence-current-of-high-voltage-side,-medium-voltage-side-and-the-reference-current.-So-the-internal-fault-and-external-fault-can-be-discriminated.-The-results-of-dynamic-simulation-experiment-and-digital-simulation-shows-that-the-proposed-method-can-detect-turn-to-ground-and-turn-to-turn-fault-with-high-sensitivity-and-good-selectivity.-Besides,-the-protection-criterion-is-not-affected-both-by-the-non-periodic-component-of-zero-sequence-current-and-saturation-level-of-fault-side-current-transformer-(CT).