Icing Flashover Characteristics of EHV AC Transmission Line Insulator Strings
HUANG Dao-chun,LIU Yun-peng,HU Yi,CAI Wei,CHEN Yong,RUAN Jiang-jun,YU Tao,YAO Tao,XU Zuo-ming,GAO Song,LU Jie
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.03.016
2009-01-01
Abstract:The insulation performance of insulators will decrease greatly when under the combined conditions of ice-covering, snow-covering, pollution and high altitudes, hence the flashover characteristics research is very meaningful. The icing flashover characteristics of energized EHV transmission line insulator strings are studied in this paper. The influence of pollution, grading rings (including simulative conductor) are considered. The research results indicate that: 1) equipped with the given grading ring and simulative conductor, under the ρSDD=0.1, 0.05, 0.025 mg/cm2 and the heavy icing conditions, the flashover voltages of 28 units XWP2-160 are 20.5% lower, 13.1% lower and 2.3% higher than the 500 kV transmission line rated phase to earth voltage respectively, those are 18.7% lower, 12.0% lower and 4.3% higher for the FXBW4-500/160 composite insulator respectively; 2) under the ρSDD=0.1 mg/cm2 and the heavy icing conditions, the flashover voltage without grading ring and simulative conductor is 11.6% higher than that with grading ring and simulative conductor. The research results can be a reference for the insulator strings icing flashover characteristics tests and external insulation coordination of EHV transmission lines in the heavy icing regions of China.