Icing Flashover Leakage Current of Long Insulator Strings in 500 Kv Transmission Line

CAI Wei,YU Tao,LIU Yun-peng,HU Yi,YAO Tao,CHEN Yong,HUANG Dao-chun,XU Zuo-ming,GAO Song,LU Jie
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.10.019
2009-01-01
Abstract:In order to provide a reference to the overhead transmission line external insulation coordination for the heavy icing and pollution regions of China,500 kV long insulator string pre-contaminated icing flashover was tested in the artificial climate laboratory at State Grid Electric Power Research Institute(SGEPRI)of SGCC.Based on the virtual instrument,a leakage current measurement system used to test the icing flashover leakage current was developed with current transformer,and the precision of this system was also tested.The research results indicate that,the leakage current can reflect the process of icing flashover,and the leakage current's change and development are closely related to the discharge process and the ice melting state of insulator strings.In the voltage withstand test,whether the partial arc can finally develop to be flashover or not is obviously represented by the waveform of leakage current and the change trend of leakage current.Hence,the leakage current can be used as an online monitoring parameter for forecasting the insulator string flashover of icing regime or melting regime.