Icing Flashover Characteristics of 500 Kv AC Post Insulators

LIU Yun-peng,XU Zuo-ming,HU Yi,WAN Qi-fa,WU Xiong,CAI Wei,YAO Tao,XU Tao,LU Jie,HUANG Dao-chun
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.07.023
2010-01-01
Abstract:In order to analyze the icing flashover characteristics of post insulators,the icing flashover characteristics of energized 500 kV post insulators were studied in a large scale artificial climate chamber at ultra high voltage (UHV)AC test base of SGCC. The state of icing,the discharge process of 500 kV post insulators and influence of pollution were discussed. The research results indicate that,under the ρSDD=0.1,0.05,0.025 mg/cm2 and the heavy icing conditions,the flashover voltages of 500 kV post insulators are 28% lower,15.1% lower and 6.1% higher than the 500 kV rated phase to earth voltage ,respectively; The research results can be used as reference for the post insulators icing flashover characteristics tests and external insulation coordination of transformer substation in the heavy icing regions of China.