Abstract:In order to analyze the icing flashover characteristics of post insulators with composite assistant shed(CAS),we investigated the performance of energized 500 kV post insulators in the presence and absence of CAS by icing test in a large-scale artificial climate chamber,and analyzed the difference of ice appearance,flashover voltage,development of leakage current and discharge path between post insulators in the presence and absence of CAS.Test results demonstrate that CAS can decelerate icicle development in the insulators and the sheds will not be bridged by icicle,which results in its discharge path mainly along the icicle and air gaps.Due to the composite antipollution shed,in the condition of being seriously iced and polluted,the flashover voltage of 500 kV station post insulators is higher than the maximum running phase to earth voltage,which is 58% higher than normal post insulators.