The Effect of Hydrophilic Coating on Airside Performance of Split Fin-and-Tube Heat Exchangers under Wet Conditions

MA Xiao-kui,DING Guo-liang,ZHANG Yuan-ming
DOI: https://doi.org/10.3321/j.issn:1006-2467.2007.12.002
2007-01-01
Abstract:The air side heat transfer and friction characteristics of split finand-tube heat exchangers with and without hydrophilic coating were experimentally studied under wet conditions.The effects of hydrophilic coating on air side performance were investigated.The results indicate that the heat transfer performance for hydrophilic coating surface is lower than the corresponding uncoated surface tested at the same wet conditions.Further,the degradation becomes more remarkable with the decrease of fin pitch and inlet air velocity,and the degradation may be up to 25.4% for same structural parameters fin-and-tube heat exchanger.The pressure drops on the hydrophilic coating surface is lower than the corresponding uncoated surface,and a maximum 51% reduction is observed.The proposed correlations of heat transfer coefficient ratio and pressure drop ratio for the heat exchanger with and without hydrophilic coating have a mean deviation of 5.6% and 8.4% from experimental data respectively and can cover 93.4% and 84.2% respectively of the experimental data within the deviation limit of ±15%.