Effect Of Corrugation Angle Of Fin On Performance Of A Wavy Finned Tube Heat Exchanger Under Constant Fan Power Condition

Jingchun Min,Xiaomin Wu,Xiaofeng Peng,Ralph L. Webb
2001-01-01
Abstract:This paper deals with the air/water wavy finned tube heat exchanger (coil). The paper discusses the effect of corrugation angle of fin on coil performance under constant fan power and fixed flow frontal area conditions. A quantitative method for simulating the heat transfer and pressure drop occurring in en exchanger is presented. The simulation considers both the air and water flows. The tube-side heat transfer coefficient was evaluated using the Petukhov equation. The air-side heat transfer coefficient and pressure drop were calculated using the Kim et al. correlations for the wavy fins and Gray/Webb correlations for the plain fin that serves as the baseline fin geometry. Performance comparisons were made for three different wavy fin geometries under constant air fan power and fixed flow frontal area conditions. The corrugation angles of the three wavy fins were 10, 13 and 17 degrees, respectively. The calculation results show that the exchanger heat transfer rate decreases as the corrugation angle of fin increases. The wavy fin with 10 degrees corrugation angle yields a heat transfer rate comparable to that of the plain fin while that with 17 degrees corrugation angle gives a heat transfer rate slightly lower than for the plain fin.