Numerical Investigation Of Effect Of Tube Shape On Air-Side Heat Transfer And Pressure Drop Characteristics Of A Finned Tube Heat Exchanger

Jc Min,Rl Webb,Xf Peng
2000-01-01
Abstract:This paper discusses the effects of tube shape on the air-side performance of a multi-row finned tube heat exchanger having herringbone wavy fins. The air-side heat transfer and pressure drop characteristics of the heat exchanger were numerically predicted using the Fluent CFD code. The numerical calculations were performed in three dimensions for two frontal air velocities of 2.54 and 3.39 m/s yielding hydraulic diameter Reynolds numbers of 770 and 1150. Investigated were five tube geometries including a round tube, three elliptical oval tubes and a flat oval tube. The round tube has a 15.875 mm (5/8 in) outside diameter and serves as the baseline tube. The four oval tubes are made by reforming the baseline round tube and have the same perimeter as that of the round tube. The aspect ratios of the three elliptical tubes are 2.00, 3.00 and 4.29 respectively and the aspect ratio of the flat oval tube is 3.00. When the tube aspect ratio is increased the air-side heat transfer coefficient and pressure drop decrease. At 2.54 mis frontal velocity, the 3.00 aspect ratio elliptical tube yields a 9.0% lower air-side heat transfer coefficient and a 48.7% lower air pressure drop than the round tube. As compared to the 3.00 aspect ratio elliptical tube, the same aspect ratio flat tube has a 2.3% higher air-side heat transfer coefficient and a 6.0% higher air pressure drop.