Novel Approach to Enhance Lightning Withstanding Level of 500 kV Transmission Line Along Mountain Sides

Junbo Deng,Jie Guo,Wei Shi,Yanhua Han
DOI: https://doi.org/10.3321/j.issn:0253-987X.2006.04.024
2006-01-01
Abstract:To enhance lightning withstanding level of 500 kV transmission line along mountainsides, a novel approach was proposed. The efficiency and economy of this method was approved by the theoretical analysis and the result of simulation. By equipping a single metal-oxide surge arrester (MOA) on the outside phase easy to be struck by lightning and the unbalanced insulation by increasing the length of insulator on the other outside phase, the transmission line withstanding level was greatly enhanced and the flashover rate of the insulators was reduced by about 90%, while the increased investment was only 33% of the traditional method by equipping three MOAs.