Statistics and Simulation of Lightning Trip Out of Transmission Lines in Guangzhou Area
Guojun LU,Jianbin LUO,Hanbo LIU,Zezhong WANG,Yinan GENG,Zhanqing YU,Rong ZENG
DOI: https://doi.org/10.13336/j.1003-6520.hve.20180430020
2018-01-01
Abstract:Lightning is a threat to the safe and reliable operation of power grid. Guangzhou region is one of the most intense regions of the lightning activity. The lightning protection of power grid in Guangzhou can be used for other regions. Therefore, based on the operation data of the transmission line, the lightning activities and the distribution of lightning trips in Guangzhou were analyzed. Based on the analysis of the lightning characteristics of typical transmission lines in Guangzhou, the lightning strike process was analyzed by the full wave process theory, and the lightning shielding failure was analyzed by the leader progression model. Moreover, the influences of terrain types, topographic parameters on lightning trip rate of transmission line of different voltage levels were analyzed. The results show that the number of lightning trip is correlated to the lightning frequency. Shielding failure flashover rate is much higher than the back striking flashover rate for 500 kV lines. Shielding failure outage rate is close to the back striking flashover rate for 220 kV lines, which is related to tower, topography and other factors. The back striking flashover rate is relatively higher than shielding failure flashover rate for 110 kV line, and in some regions it is significantly higher. The lightning trip rate in the regions of the mountain, ridges and valleys is significantly higher than that in the flat ground region, and it increases with the increase of slope and valley depth.