Study on Lightning Backlash Trip Rate and Lightning Resistance Level after AC to DC Operation of Transmission Lines

Qing Wu,Xueqin Zhang,Yujun Guo,Song Xiao,Guangning Wu
DOI: https://doi.org/10.1109/psgec58411.2023.10255920
2023-01-01
Abstract:After the transmission line changed from AC to DC operation, The tower foundations and conductors of the original AC line are generally not replaced, but are only changed to DC by relocating the conductors and grounding devices. the line lightning attraction capability as well as the lightning protection level changed due to the change in the spatial electric field. In this study, ATP-EMTP simulation software was used to model AC and DC transmission lines under the same lightning protection measures, and the differences in lightning resistance levels and lightning strike trip rates between the two when subjected to lightning strikes back on the towers were compared through simulation analysis. The simulation results show that compared with AC operation, the lightning resistance level of DC transmission lines is reduced by 10.2% and the lightning strike trip rate is significantly reduced by 19.97%, reducing the tower grounding resistance plays an important role in improving the lightning resistance level of AC to DC transmission lines and the lightning strike trip rate, and the lightning resistance level and trip rate of AC and DC operation transmission lines with tower grounding resistance of $1-5\Omega$ are rate have reached a high safety level.