NEW RESONANCE EARTH SYSTEM WITH MAGNETIC BIAS AND ITS PROTECTION

蔡旭,刘勇,胡春强,左红艳
DOI: https://doi.org/10.3321/j.issn:0258-8013.2004.06.009
2004-01-01
Abstract:Systematic studies of a resonance earth system with magnetic bias and its protection are proposed. A structure of arc-suppression coil with magnetic bias is presented. It consists of an iron core with three columns and five coils. The cross-section of the two side columns is cut down partly by two grades and the diminished parts act as the area where the magnetization occurs. By injecting current with 50 HZ into the neutral point, the capacity current of the network is measured so that the arc-suppression can be correctly tuned. Two detection algorithms for earth faults named increment function are proposed, one of which is zero current increment function used in permanent earth fault and the other is zero energy increment function used in transient earth faults. A set of equipment of resonance earth and protection is developed. It is proved that the arc-suppression with magnetic bias can be effectively used and the equipment based on increment function principle can detect correctly earth faults by over one year test on the power system.
What problem does this paper attempt to address?