Study of special problems on protective relaying of uhv transmission line

董新洲,苏斌,薄志谦,贺家李
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.22.004
2004-01-01
Abstract:This paper discusses two special problems on relay protection of ultra-high voltage (UHV) transmission line: one is the effect of protection relay operation order on surge voltage, and another is the influence of charge current caused by distributed capacitances in UHV long transmission line on the current differential protection. Theoretical analysis and simulation results show that: adjusting protection relay operation order can effectively limit the surge voltage formed by the operation of circuit breaker, and the existed phase current differential protection with no compensation measurements is unsuitable for UHV transmission lines.
What problem does this paper attempt to address?