Analysis of negative sequence protection operation characteristics for uhv AC transmission line

TANG Feng,YUAN Yue,WANG Bin,DONG Xin-zhou
2007-01-01
Abstract:Negative sequence protection is widely used in Extra-High-Voltage line protection due to its immunity of path resistance and system oscillation.However,there are new problems for this protection in Ultra-High-Voltage system due to the larger shunt capacitance and intensive fault transients.In this paper,the characteristics of negative sequence protection adapted to UHV system is discussed.Therotical anaylsis and simulation result have proved that the negative sequence relay is capable of reliable operation under asymmetry fault on UHV lines,and it is immune from path resistance and fault distance.As negative sequence impedance is hyperbolic function with fault location,negative sequence relay will misoperation on very long lines without shunt reactors.Also due to transient interference and its impact on the relay’s sensitivity,a better-performanced digital filter should be taken into consideration..
What problem does this paper attempt to address?