Abstract:It is well-known the transients of CVT won't result in the maloperation of direction protection.However,with large amounts of simulation,this paper finds out that when there is little zero-sequence(negative-sequence) voltage,the zero-sequence direction relay or negative-sequence direction relay has the possibility of maloperation which should be paid attention to.Besides,zero-sequence and negative-sequence direction relay won't maloperate at the same time under the same condition.Based on all of the above,a new method on the zero-sequence and negative-sequence direction relay is put forward to improve the security of direction protection.